Standard and safety communication in a single module
Text Murrelektronik, Evi HussonImage Murrelektronik

Making complex configurations simple. That is what Murrelektronik’s new MVK Fusion CIP Safety module does. The Ethernet/IP CIP Safety module combines three essential functions of installation technology: standard digital sensors and actuators, safety-related digital sensors and actuators, and IO-Link. This offers attractive possibilities for a wide range of automation applications.
Making industrial automation as simple, well thought-out and cost-effective as possible with smart solutions. That is Murrelektronik’s speciality. With its MVK Fusion fieldbus module, the company aims to standardise modular processes. The latest addition to the range is the MVK Fusion CIP Safety. This three-in-one solution combines three key functions of installation technology: standard digital I/O, safety digital I/O and IO-Link. This means fewer fieldbus modules are needed for each modular unit, in the best case just one. Installation is therefore simpler and faster.
Simple configuration
MVK Fusion CIP Safety significantly simplifies the configuration of safety-related sensors and actuators. Parameters can easily be set in the controller manufacturer’s engineering tool. No special tool is needed to transfer the SNN (Safety Network Number) to a new device. This saves time and reduces stress by eliminating the possibility of incorrect entries.

Safety output (FDO)
The MVK Fusion CIP Safety module has several M12 ports. Port X3 is a safe digital output. It is a powerful and flexible solution for a range of applications, with the following features: up to 2 A per channel; one or two safety outputs per I/O port; configurable output behaviour (P-P, P-M, P-P-M); control of different types of actuators, including double valves; and high diagnostic coverage through a dark test.
Safety input (FDI)
The safe input ports X0, X1 and X2, each with two channels, register signals from typical safety sensors up to the maximum Performance Level e. The ports are protected against short circuits and overloads and have a robust 24 VDC/700 mA power supply. Parameters such as discrepancy, input delay and sensor polarity can be configured, and individual test pulses can be used to detect peripheral faults.
IO-Link
The IO-Link ports X6 and X7 enable the cost-effective integration of complex sensors and actuators into the fieldbus system and extend standard digital signals. Up to 32 additional DIOs can be added using IO-Link hubs. IO-Link devices can also be safely switched off up to Performance Level d using the Class B IO-Link port X7.

DIO
The digital ports X4 and X5 offer maximum flexibility and efficiency. They can be used as inputs or outputs. The outputs deliver up to 2 A per channel. An input delay adjustable from 1 to 15 milliseconds is available. The port is protected against reverse polarity, short circuits and overloads.
Ethernet and power
The MVK Fusion CIP Safety has M12 D-coded Ethernet ports for communication with the controller and daisy-chaining the fieldbus. The module has M12 Power L-coded connections for its power supply. The power supply can be daisy-chained via port XD2 up to a maximum of 16 A.
Demanding environments
The MVK Fusion CIP Safety is suitable for demanding environments. It has a robust, potted metal housing, is IP67-certified, resistant to shock and vibration, and can withstand temperatures from -30 °C to +60 °C.
Adapters
Various adapters are available to simplify the connection of devices with safety and standard signals. Configurable sourcing bipolar safety outputs can be used for Safe Torque Off. Configurable single or redundant safety inputs are suitable for standard safety contacts or OSSD devices. Many devices, such as emergency stops with a reset button or interlocks, require a combination of safety and standard signals.

In just a few clicks
In short, the MVK Fusion CIP Safety significantly simplifies the configuration of safety-related sensors and actuators. It makes complex configurations simple, perfectly reflecting Murrelektronik’s philosophy: making machine and plant automation simpler, faster and more cost-effective.
A business enquiry for Murrelektronik? Get in touch
Companies in this story